NBC 16

In this section, some guidelines are given in NCB 16 which are to be taken care while doing electrical work. These guidelines cover following topics –

7.1 Ceiling Roses and Similar Attachments

7.2 Socket-Outlets and Plugs

7.3  Lighting Fittings

7.4 Fitting-Wire

7.5 Lamp holders

7.6 Outdoor Lamps

7.7 Lamps

7.8 Fans, Regulators and Clamps

7.9 Attachment of Fittings and Accessories

7.10 Interchangeability

7.11 Equipment

Detail is each section is given below –

7.1 Ceiling Roses and Similar Attachments

 

7.1.1. A ceiling rose or any other similar attachment shall not be used on a circuit the voltage of which normally exceeds 250 V.

7.1.2. Normally, only one flexible cord shall be attached to a ceiling rose. Specially designed ceiling roses shall be used for multiple pendants.

7.1.3 A ceiling rose shall not embody fuse terminal as an integral part of it.

 

7.2 Socket-Outlets and Plugs

Each 16 A socket-outlet provided in buildings for the use of domestic appliances, such as, air conditioner and water cooler shall be provided with its own individual fuse, with suitable discrimination with back-up fuse or miniature circuit-breaker provided in the distribution/sub-distribution board. The socket-outlet shall not necessarily embody the fuse as an integral part of it.

7.2.1 Each socket-outlet shall also be controlled by a switch which shall preferably be located immediately adjacent thereto or combined therewith.

7.2.2 The switch controlling the socket-outlet shall be on the live side of the line.

7.2.3 Ordinary socket-outlet may be fixed at any convenient place at a height above 200 mm from the floor level and shall be away from danger of mechanical injury.

NOTE . In situations where a socket-outlet is accessible to children, it is necessary to install an interlocked plug and socket or  alternatively  a  socket-outlet which  automatically  gets screened by the withdrawal of plug. In industrial premises socket-outlet of rating 20 A and above shall preferably be provided with interlocked type switch.

In case of public buildings, to facilitate operation of switches/socket-outlets by persons with disabilities and the elderly, these shall be installed at an accessible height for reaching and operating, between 800 mm and 1 100 mm above floor level and shall be located at  a minimum  of  600 mm with  a  preference  of minimum 700 mm, from any internal corner (see also B-7  of  Part  3  ‘Development  Control  Rules  and General Building Requirements’ of the Code). They shall be so fixed so as to be away from danger of mechanical injury.

NOTE . As  an  exception,  electrical wall  socket  outlets, telephone points and TV sockets can be located at a minimum height of 400 mm above floor level.

7.2.4 In an earthed system of supply, a socket-outlet with plug shall be of three-pin or five-pin type with the third or fifth terminal connected to the earth. When such socket-outlets with plugs are connected to any current  consuming  device  of metal  or  any  non-insulating material or both, conductors connecting such current-consuming devices shall be of flexible cord with an earthing core and the earthing core shall be secured by connecting between the earth terminal of plug and the body of current-consuming devices.

In industrial premises three-phase and neutral socket-outlets shall be provided with a earth terminal either of pin type or scrapping type in addition to the main pins required for the purpose.

7.2.5 In wiring installations for residential buildings, metal clad switch, socket-outlet and plugs shall be used for  power wiring.  For  industrial  and  commercial application socket outlets conforming to accepted standards [8-2(25)] with suitable circuit breakers shall be used.

NOTE . A recommended schedule of socket-outlets in a residential building is given below:

S. No

Location Number of 6A Socket Outlets Number of 16A Socket Outlets
i) Bed room 2 to 6

2

ii)

Living room 2 to 4 2

iii)

Kitchen 2 to 8 2

iv)

Dining room 2 to 8

2

v)

Garage 1 1

vi)

For Refrigerator

1

vii)

For Air -conditioner

1 for each

viii)

Verandah 1 per 10 sq mtr 1
ix) Bathroom 1

1

 

7.3 Lighting Fittings

7.3.1 A switch shall be provided for control of every lighting fitting or a group of lighting fittings. Where control at more than one point is necessary as many two way or intermediate switches may be provided as there are control points. See also 7.2.3.

7.3.2 In industrial premises, lighting fittings shall be supported by suitable pipe/conduits, brackets fabricated from structural steel, steel chains or similar materials depending upon the type and weight of the fittings. Where a lighting fitting is supported by one or more flexible cords, the maximum weight to which the twin flexible cords may be subjected shall be as follows:

S. No

Nominal Cross Sectional Area of Twin Cord mm2

Maximum Permissible Weight Kg

i)

0.5 2

ii)

0.75

3

iii) 1.0

5

iv)

1.5 5.3

v)

2.5 8.8

vi)

4

14.0

7.3.3 No flammable shade shall form a part of lighting fittings unless such shade is well protected against all risks of fire. Celluloid shade or lighting fittings shall not be used under any circumstances.

7.3.4 General and safety requirements for electrical lighting fittings shall be in accordance with good practice [8-2(40)].

7.3.5 The lighting fittings shall conform to accepted standards [8-2(26)].

 

7.4 Fitting-Wire

The use of fitting-wire shall be restricted to the internal wiring of the lighting fittings. Where fitting-wire is used for wiring fittings, the sub-circuit loads shall terminate in a ceiling rose or box with connectors from which they shall be carried into the fittings.

 

7.5 Lamp holders

Lamp holders for use on brackets and the like shall be in accordance with accepted standards [8-2(41)] and all those for use with flexible pendants shall be provided with cord grips. All lamp holders shall be provided with shade carriers. Where center-contact Edison screw lamp holders are used, the outer or screw contacts shall be connected to the .middle wire., the neutral, the earthed conductor of the circuit.

 

7.6 Outdoor Lamps

External and road lamps shall have weatherproof fittings of approved design so as to effectively prevent the ingress of moisture and dust. Flexible cord and cord grip lamp holders shall not be used where exposed to weather. In verandahs and similar exposed situations where pendants are used, these shall be of fixed rod type.

 

7.7 Lamps

All lamps unless otherwise required and suitably protected, shall be hung at a height of not less than 2.5 m above the floor level. All electric lamps and accessories  shall  conform  to  accepted  standards [8-2(42)]. Following shall also be ensured:

a)Portable lamps shall be wired with flexible cord. Hand lamps shall be equipped with a handle  of moulded  composition  or  other material  approved  for  the  purpose. Hand lamps shall be equipped with a substantial guard attached to the lamp holder or handle. Metallic guards shall be earthed suitably.

b) A bushing or the equivalent shall be provided where flexible cord enters the base or stem of portable The  bushing  shall  be  of insulating material unless a jacketed type of cord is used.

c) All wiring shall be free from short circuits and shall be tested for these defects prior to being connected to the circuit.

d) Exposed live parts within porcelain fixtures shall be suitably recessed and so located as to make it improbable that wires will come in contact with them. There shall be a spacing of at least 125 mm between live parts and the mounting plane of the fixture.

 

7.8 Fans, Regulators and Clamps

7.8.1 Ceiling Fans

Ceiling fans including their suspension shall conform to accepted standards [8-2(43)] and to the following requirements:

 

a)Control of a ceiling fan shall be through its own regulator as well as a switch in series. See also 7.2.3.

b) All ceiling fans shall be wired with normal wiring to ceiling roses or to special connector boxes to which fan rod wires shall be connected and suspended from hooks or shackles with insulators between hooks and suspension rods. There shall be no joint in the suspension rod, but if joints are unavoidable then such joints shall be screwed to special couplers of 50 mm minimum length and both ends of the pipes shall touch together within the couplers, and shall in addition be secured by means of split pins; alternatively, the two pipes may be welded. The suspension rod shall be of adequate strength to withstand the dead and impact forces imposed on it. Suspension rods should preferably be procured along with the fan.

c) Fan clamps shall  be  of  suitable  design according to the nature of construction of ceiling on which these clamps are to be fitted. In all cases fan clamps shall be fabricated from new metal of suitable sizes and they shall be as close fitting as possible. Fan clamps for reinforced concrete roofs shall be buried with the casting and due care shall be taken that they shall serve the purpose. Fan clamps for wooden beams, shall be of suitable flat iron fixed on two sides of the beam and according to the size and section of the beam one or twomild steel bolts passing through the beam shall hold both flat irons together. Fan clamps for steel joist shall be fabricated from flat iron to fit rigidly to the bottom flange of the beam. Care shall be taken during fabrication that the metal does not crack while hammer to shape. Other fan clamps shall be made to suit the position, but in all cases care shall be taken to see that they are rigid and safe.

d) Canopies on top and bottom of suspension rods shall effectively conceal suspensions and connections to fan motors, respectively.

e) The lead-in-wire shall be of nominal cross-sectional area not less than 1.5 mm2 copper and shall be protected from abrasion.

f) Unless otherwise specified, the clearance between the bottom most point of the ceiling fan and the floor shall be not less than 2.4 m. The minimum clearance between the ceiling and the plane of the blades shall be not less than 300 mm.

A typical arrangement of a fan clamp is given in Fig. 4.

NOTE . All fan clamps shall be so fabricated that fans revolve steadily.

7.8.2 Exhaust Fans 

For fixing of an exhaust fan, a circular hole shall be provided in the wall to suit the size of the frame which shall be fixed by means of rag-bolts embedded in the wall. The hole shall be nearly plastered with cement and brought to the original finish of the wall. The exhaust fan shall be connected to exhaust fan point which shall be wired as near to the hole as possible by means of a flexible cord, care being taken that the blades rotate in the proper direction.

7.8.3 Fannage

7.8.3.1 Where ceiling fans are provided, the bay sizes of a building, which control fan point locations, play an important part. Fans of 1 200/1 400 mm sweep normally cover an area of 9 m2 to 10 m2 and therefore in general purpose office buildings, for every part of a bay to be served by the ceiling fans, it is necessary that the bays shall be so designed that full number of fans can be suitably located for the bay, otherwise it will result in ill-ventilated pockets. In general, fans in long halls may be spaced at 3 m in both the directions. If building modules do not lend themselves for proper positioning of the required number of ceiling fans, other fans such as, air circulators or bracket fans will have to be employed for the areas uncovered by the ceiling fans. For this, suitable electrical outlets shall be provided although result will be  disproportionate to cost on account of fans.

7.8.3.2 Proper air circulation may be achieved either by larger number of smaller fans or smaller number of larger fans. The economics of the system as a whole should be a guiding factor in choosing the number and type of fans and their locations. For design guidelines in  this  regard,  reference  shall  be made  to  Part  8 .Building Services, Section 1 Lighting and Natural Ventilation. of the Code.

7.8.3.3 Exhaust fans are necessary for spaces, such as community toilets, kitchens and canteens, and godowns to provide the required number of air changes (see Part 8 .Building Services, Section 3 Air Conditioning, Heating and Mechanical Ventilation. of the Code). Since the exhaust fans are located generally on the outer walls of a room, appropriate  openings in such walls shall be provided for, in the planning stage.

NOTE  .  Exhaust  fan  requirement  is  based  on  the recommended  air changes (see Part  8  ‘Building  Services, Section  3  Air  Conditioning,  Heating  and Mechanical Ventilation’ of the Code). Reference shall also be made to Part 4 ‘Fire and Life Safety’ of the Code for exhaust fan requirements for smoke extraction.

 

7.9 Attachment of Fittings and Accessories

7.9.1 In wiring other than conduit wiring, all ceiling roses, brackets, pendants and accessories attached to walls or ceilings shall be mounted on substantial teak wood blocks twice varnished after all fixing holes are made in them. Blocks shall not be less than 40 mm deep. Brass screws shall only be used for attaching fittings and accessories to their base blocks.

7.9.2 Where teak or hardwood boards are used for mounting switches, regulators, etc, these boards shall be well varnished with pure shellac on all four sides (both inside and outside), irrespective of being painted to match the surroundings. The size of such boards shall depend on the number of accessories that can be conveniently and neatly be arranged. Where there is danger of attack by white ants, the boards shall be treated with suitable anti-termite compound and painted on both sides.

 

7.10 Interchangeability

Similar parts of all switches, lamp holders, distribution fuse-boards, ceiling roses, brackets, pendants, fans and all other fittings shall be so chosen that they are of the same type and interchangeable in each installation.

7.11 Equipment

Electrical equipment which form integral part of wiring installations  shall  conform  to  the  relevant  Indian Standards, wherever they exist.

7.12 Positioning

Positioning of fans and light fittings shall be chosen to make these effective without causing shadows and stroboscopic effect on the working planes.